The wrong type of plumbing can increase the risk of Legionnaires’ disease

SINTEF researchers have been testing different types of water distribution cabinets. Cabinets that combine the distribution of both domestic tap water and water for floor heating, are now shown to represent an unnecessary risk of Legionnaires’ disease.

Pipe-in-pipe plumbing systems on the Norwegian market are tested and approved via the SINTEF Technical Approval System. However, plumbing installed in connection with so-called combi-cabinets has not been approved. The reason for this is the risk of establishing the Legionella bacterium that can cause serious lung infection, and which claims the lives of an unknown number of people each year.

The Legionella bacterium can establish itself in the biofilm that forms on the inside of water pipes, where it can reproduce if conditions are favourable. Once the bacterium has established itself in the plumbing system, it can be difficult to get rid of.

“A commonly used method is to flush the plumbing system with hot water. Unfortunately, recent research indicates that this has little effect”, says Dag Fredrik Nedberg, who is an adviser at SINTEF Community.

Testing different distribution cabinets

In a pipe-in-pipe system, it is usually the case that heat transfer takes place between hot and cold water in the distribution cabinet. In order to investigate how different cabinet systems affect the temperature in standing cold water, we have compared the results of field measurements carried out in different types of distribution cabinets.

Combi-cabinets represent a risk of establishment of the Legionella bacterium. Photo: SINTEF

The poorest performers are the combi-cabinet systems, in which tap water and water for floor heating are installed side by side in the same cabinet. Not surprisingly, the floor heating system gives off a lot of heat. This causes the temperature in the cabinet to rise to as much as 40 °C, offering the best possible temperature range for establishment of the Legionella bacterium. Tap water is heated rapidly to the same temperature, and if the water remains standing in the system for some days, this will provide excellent growth conditions for the bacterium. Other types of distribution cabinet may also provide favourable conditions for bacterial growth, such as those connected to riser pipes, which are commonly installed in tall buildings.

Facts about the Legionella bacterium:

The Legionella bacterium is potentially fatal. Because it is difficult to get rid of, this makes it all the more important to identify water distribution systems that prevent its growth. The bacterium relies on favourable temperature conditions for its effective growth and reproduction, and temperatures of between approx. 30 and 45 °C are thought to be optimal. The bacterium can reproduce rapidly at these temperatures, especially if there is standing water in the plumbing system. The prevention of bacterial establishment is thus all about maintaining the correct temperature conditions in the water pipes. Several factors in addition to temperature influence the risk of Legionella growth, and there is still a lot we do not know. The bacterium can also establish itself in cold water.

In tall buildings, water seldom remains standing in the riser pipes, and there is a constant supply of new hot water that heats up the distribution cabinet. Our measurements showed that this type of cabinet exhibited temperatures of more than 30 °C throughout a 24-hour period, providing ideal conditions for the establishment and growth of the Legionella bacterium. (See the figure below)

An example of temperature development in a water distribution cabinet with riser pipes. Based on measurements taken by SINTEF

Keep the water as cold as possible

The prevention of bacterial growth is thus all about maintaining the correct temperature conditions in the water pipes. Cold water must be kept at low temperatures, preferably below 20 °C. In practice, this causes complications, because standing water in the plumbing system will soon acquire the same temperature as its surroundings.

According to SINTEF, cold water should be kept as cold as possible and never be allowed to become warmer than room temperature, regardless of how long it remains standing in the plumbing system. In order to achieve this, we must ensure that the cold water is not heated by other installations in the building. The best approach is to make sure that systems required to supply hot water are isolated as much as possible from cold water installations.

‘Standard’ water distribution cabinets, which supply only hot and cold tap water, performed surprisingly well during the SINTEF investigation. Even if the hot water system releases some heat, the temperature in the cabinets remained only a few degrees above room temperature.

“If we are to completely avoid heat transfer in our tap water systems, the best approach is to install the hot and cold water systems in separate cabinets. However, we believe that standard distribution cabinets accommodating both hot and cold tap water represent an acceptable solution”, says Dag Fredrik Nedberg.